Field setting mode
English
Field Setting Mode
3023: Offset temperature of DHW’s thermo on (Only Hydro Unit / Not Hydro Unit HT)
ƟʪΧʪθɇϩЇθʪͱ˙²ͱϩǮɇϩʪθƟɇƊʪϩϩ˝ϩʪΧʪθɇϩЇθʪͱ˙²ͱϩǮɇϩʪθƟɇߢ
ĘUƟʪΧʪθɇϩЇθʪͱ˙²ͱϩǮɇϩʪθƟɇAͱʒʪࢄߤߡߣߢࣔAͱʒʪࢄߤߡߣߣAͱʒʪࢄߤߡߣߤ
3024: When Heating and DHW mode is operating at the same time and heating mode is operating
based on leaving water temperature with Thermo off, heating will operate for number of
minutes stated in #3024 after every time maximum DHW operation time ends
3025: DHW operation time when heating and DHW mode is operating at the same time
3026: Heating operation time when heating and DHW mode is operating at the same time
303*: Booster heater variables for combination with heat pump
3031: Application of Booster heater
3032: Booster heater startup delay timer
ߤߡߤߤࡠ9ͱͱϑϩʪθ˵ʪɇϩʪθͱЭʪθϑ˵ͱͱϩϩʪΧʪθɇϩЇθʪ࣍ƊǤࢄߤߡߤߤࡡUʪ˙ɇЇϩࣨߡઑAࣩࡡŵɇ˝ʪߡߥઑA࣎
304*: Setting hot water tank disinfection period
3041: Application of disinfection function
3042: Scheduling (day)
Sunday Monday Tuesday Wednesday Thursday Friday Saturday AllDay
01234567
3043: Starting time (hour)
3044: Target tank temp
3045: Duration time (After reaching the target temperature)
3046: Maximum duration of disinfection operation (disinfection operation stops after the specified
duration)
Disinfection operation can start if a booster heater is connected.
Check the booster heater capacity and booster heater failure , if disinfection operation does not
work normally over the maximum duration. (E919 error)
3061: Interlock between solar pump and hot water
0: Hydro unit ‘s operation regardless of solar pump activation
1: Hydro unit’s stop when solar pump is operating
2: Disabled
3: Defrost signal output when entering defrost mode
Code 401*
Space/DHW heating priority and control variables
4011: Priority setting of simultaneous operation both hot water and heating
0: Hot water operation has priority. (The related operation is followed with 302*)
1: Heating operation has priority. (If an ambient temperature < 4012, hot water operation is
neglected.)