Field Setting Mode
࡙ 4012 : The temperature of forced heating priority (Refer to 4011)
࡙ 4013 : If the ambient temperature > 4013, Heating Mode stops in auto mode.
࡙ Code 50**
ࣕ User’s options for extra functions
501*: New target temperatures of each mode (Heating/Cooling/DHW) when “Outing” function is on
࡙ 5011: Value of cooling leaving water temperature setting when “Outing” function is on
࡙ 5012: Value of cooling indoor’s room temperature setting when”Outing” function is on
࡙ 5013: Value of heating leaving water temperature setting when “Outing” function is on
࡙ 5014: Value of heating indoor’s room temperature setting when”Outing” function is on
࡙ 5017: Value of Water Law’s floor control (#2041=1) leaving water temperature setting when “Outing”
function is on
࡙ ߦߡߢߩࡠǤɇЇʪͱ˙Ǯɇϩʪθøɇи࣭ϑAƸʀͱϩθͱ࣍ࢄߣߡߥߢߣ࣎ʪɇЭ˝иɇϩʪθϩʪΧʪθɇϩЇθʪϑʪϩϩ˝и˵ʪࣨĮЇϩ˝ࣩ
function is on
࡙ 5019: Value of DHW tank’s temperature setting
5021: Offset temperature setting when Economic DHW operation is on (During Economic DHW
operation, temperature will be automatically set lower by value of #5021(°C) than actual setting)
504*: Smart Grid control
࡙ 5041: Application of Smart Grid control
࡙ 5042: Heater application during Smart Grid control
ࣕ 0: Heater off during Smart Grid control
ࣕ 1: Heater control during Smart Grid control
ࣕ 2: Not use
࡙ 5043: Input Voltage from Smart Grid contact port
ࣕ 0: If Smart Grid Voltage = 0V, Smart Grid Control is Operated
ࣕ 1: If Smart Grid Voltage = 5V, Smart Grid Control is Operated
࡙ 5061: Water supply capacity ratio compared to heating: The load of hot water tank if designed
heating (floor or Fan coil unit) load is 7
ex) When required heating load is 14000W, required hot water tank load 10000W, 10000/14000x7= Set 5