Field Setting Mode
Air to Water Heat Pump: Only AE*** Model
CAUTION
࡙ Set the FSV value of the product other than the specified models by referring to the FSV label provided
with the manual of the product, and then attach it on the control box's cover. The FSV values in the table
are applied to the specified models.
NOTE
࡙ Be sure to reset the power when changing the FSV (#3041 to 3046) of disinfection operation and the
FSV (#5011 to 5019) of setting the outing mode.
Field Setting Value (FSV) 10**
Code 10** : Upper and lower temperature limits of each operation mode of wired remote controller
Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)
࡙ The values in the following table are just examples for your understanding.
Main Menu
& Code
Menu
Function
Sub
Code
MODEL CODE :
AE200(260)RNW***
MODEL CODE :
MIM-E03CN /
MIM-E03EN
Setting Standard Setting Standard
Item Step Unit Default Min. Max. Default Min. Max.
Remote
Controller
Setting
Range Code
10**
Cooling
Water Out Temperature for
Cooling
Max 1 ঐ 1011 25 ߢߩ 25 25 ߢߩ 25
Min 1 ঐ 1012 16 5 ߢߩ 16 5 ߢߩ
Room Temperature for
Cooling
Max 1 ঐ 1021 30 ߣߩ 30 30 ߣߩ 30
Min 1 ঐ 1022 ߢߩ ߢߩ ߣߩ ߢߩ ߢߩ ߣߩ
Heating
Water Out Temperature for
Heating
Max 1 ঐ 1031 65/70
1)*
37 65/70
1)*
65/70
1)*
37 65/70
1)*
Min 1 ঐ 1032 25 15 37 25 15 37
Room Temperature for
Heating
Max 1 ঐ 1041 30 ߢߩ 30 30 ߢߩ 30
Min 1 ঐ 1042 16 16 ߢߩ 16 16 ߢߩ
DHW DHW tank Temperature
Max 1 ঐ 1051 55 50 70 55 50 70
Min 1 ঐ 1052 40 30 40 40 30 40
NOTE
࡙ The FSV #3011 in the wired remote controller should be set to 1 or 2 to use the DHW mode.
࡙
1)*
The value is determined according to the type of outdoor unit.
Field setting mode