Field setting mode
English
Field Setting Mode
Classification Function Detail
Code
(Main
+ sub
menu)
Basic Min. Max. Step Unit
Others
Ratio of hot water supply
compare to heating
A/7 (Ratio is
determined based
on the value of the
A)7 means Heating
capacity=Hot water
capacity
5061 7 1 7 1 -
NOTE
The menu not supported by the product will not be displayed.
DVM Hydro unit HT: Only AM***TNBF** Model
The values in the following table are just examples for your understanding.
Classification Function Detail
Code
(Main
+ sub
menu)
Basic Min. Max. Step Unit
Remote
controller
Temperature of general
cooling leaving water
Max. 1011 - - - 1 °C
Min. 1012 - - - 1 °C
General indoor cooling
temperature
Max. 1021 - - - 1 °C
Min. 1022 - - - 1 °C
Temperature of general
heating leaving water
Max. 1031 ߩߡ 40 ߩߡ C
Min. 1032 25 25 40 1 °C
General indoor heating
temperature
Max. 1041 30 ߢߩ 30 1 °C
Min. 1042 16 16 ߢߩ C
Temperature of hot water
tank
Max. 1051 70 45 75 1 °C
Min. 1052 45 35 45 1 °C
Water Law
Auto heating ambient
temperature
Max. 2011 -10 -20 5 1 °C
Min. 2012 15 10 20 1 °C
Temperature of auto
heating leaving water
(WL1-Floor)
Max. 2021 45 35 ߩߡ C
Min. 2022 30 25 ߩߡ C
Temperature of auto
heating leaving water
(WL2-FCU)
Max. 2031 50 35 ߩߡ C
Min. 2032 35 25 ߩߡ C