30
Field setting mode
English
Field Setting Mode
Field Setting Value (FSV) 30**
Code 30** : User’s options for Domestic Hot Water(DHW) tank heating
࡙ The values in the following table are just examples for your understanding.
Main Menu &
Code
Menu
Function
Sub
Code
MODEL CODE :
AE200(260)RNW***
MODEL CODE :
MIM-E03CN /
MIM-E03EN
Setting Standard Setting Standard
Item Step Unit Default Min. Max. Default Min. Max.
Domestic
Hot Water
Tank
Code 30**
DHW
DHW mode
activate
DHW mode - - 3011 1 0 2 0 0 2
Heat Pump
Max. Temp. 1 ઑA 3021 55 45 55 55 45 55
Stop 1 ઑA 3022 0 0 10 2 0 10
Start 1 ઑA 3023 5 5 30 5 5 30
Min. Operating
Time
1 min 3024 5 1 20 5 1 20
Max. Operating
Time
5 min 3025 30 5 95 30 5 95
Operation
Interval
0.5 hour 3026 3 0.5 10 3 0.5 10
Booster
Heater
On/Off - - 3031 1 (On) 0 (Off) 1 1 (On) 0 (Off) 1
Delay Time 5 min 3032 20 20 95 20 20 95
Overshoot 1 ઑA 3033 0 0 4 0 0 4
Disinfection
On/Off - - 3041 1 (On) 0 (Off) 1 1 (On) 0 (Off) 1
Interval 1 day 3042 Fri (5)
Sun (0)
All (7) Fri (5)
Sun (0)
All (7)
Start Time 1 o'clock 3043 23 0 23 23 0 23
Target Temp. 5 ઑA 3044 70 40 70 70 40 70
Duration 5 min 3045 10 5 60 10 5 60
Max time 1 hour 3046 ߩ 124 ߩ 124
Forced DHW
Operation
Timer OFF
Function
- - 3051 0 (No) 0 1 (Yes) 0 (No) 0 1 (Yes)
Time Duration 1
(x10)
min
3052 6 3 30 6 3 30
Solar Panel/
DHW
Thermostat
H/P
Combination
1 - 3061 0 (No) 0 2 0 (No) 0 2
3-way Valve Defalut Direction - - 3071
0 (Room) 0 1 (Tank) 0 (Room) 0 1 (Tank)