36
Field setting mode
English
Field Setting Mode
Field Setting Value (FSV) 40**
Code 40** : User’s options for heating devices including internal backup heater and external boiler
࡙ The values in the following table are just examples for your understanding.
Main Menu &
Code
Menu
Function
Sub
Code
MODEL CODE :
AE200(260)RNW***
MODEL CODE :
MIM-E03CN / MIM-E03EN
Setting Standard Setting Standard
Item Step Unit Default Min. Max. Default Min. Max.
Heating
Code 40**
Heating
Heat
Pump
Heating / DHW
priority
- - 4011 0 (DHW) 0
1
(Heating)
0 (DHW) 0
1
(Heating)
Low Outdoor Temp.
for
Heating Priority
1 ઑA 4012 0 -15 20 0 -15 20
Heating Off Temp . 1 ઑA 4013 35/45
1)*
14 35/45
1)*
35/45
1)*
14 35/45
1)*
Backup
Heater
On/Off - - 4021 0 (No) 0 2 0 (No) 0 2
BUH/BSH Priority 1 - 4022 2 (BSH)
0 (Both)
2 (BSH) 0 (Both) 0 2 (BSH)
Cold weather
compensation
- - 4023 1 (Yes) 0 (No) 1 1 (Yes)
0
(No)
1
Threshold Temp. 1 ઑA 4024 0 -25 35 0 -25 35
Defrost Backup
Temp.
5 ઑA 4025 15 10 55 15 10 55
Backup
Boiler
Back-up Boiler On/Off
- - 4031 0 (No) 0 1 (Yes) 0 (No) 0 1 (Yes)
Boiler Priority - - 4032 0 (No) 0 1 (Yes) 0 (No) 0 1 (Yes)
Threshold Condition 1 ઑA 4033 -15 -20 5 -15 -20 5
Mixing
valve
Application 1 - 4041 0 (No) 0 2 0 (No) 0 2
Ɵɇθ˝ʪϩƟ࣍²ʪɇϩ˝࣎ 1 ઑA 4042 10 5 15 10 5 15
Ɵɇθ˝ʪϩƟ࣍Aͱͱ˝࣎ 1 ઑA 4043 10 5 15 10 5 15
Control factor 1 - 4044 2 1 5 2 1 5
Control interval 1 min 4045 2 1 30 2 1 30
Running Time 3
(x10)
min
4046 9 6 24 9 6 24
Inverter
Pump
Application - - 4051 1 0 2 1 0 2
Ɵɇθ˝ʪϩƟ 1 ઑA 4052 5 2 ߩ 52 ߩ
Control factor 1 - 4053 2 1 3 2 1 3
Addition
Function
Zone controll 1 - 4061 0 (No) 0 1 (Yes) 0 (No) 0 1 (Yes)
NOTE
࡙
1)*
The value is determined according to the type of outdoor unit.
࡙ MIM-E03CN model does not support this Zone control function.