19
Installation/Service mode
Step 1 Step 2 Step 3 Description Default
Heat pump options
Activating hot water
function (3011)
Note 3)
Used / Not used
When Used is
selected, select from
Control hot water
thermo type 1 and
Control hot water
thermo type 2
Used / Not used
(*1)
Using the thermostat
(2091,2092)
Thermostat #1 UFHs (2091)
Used / Not used
Thermostat #2 FCUs (2092)
Used / Not used
Not used
Room temperature
control (2093)
Thermo on/off by
room sensor /
Thermo on/off by
Water Law
Thermo on/off by
Water Law
When
Water Law
is selected, select
from Pump off when
thermo is off, Pump
on when thermo is off,
and Pump on/off when
thermo is off
Pump on/off when
thermo is off
Energy metering (3081, 3083)
Backup heater capacity (3081)
1kw to 6kw 2kw
Booster heater capacity (3083)
1kw to 6kw 3kw
Solar panel / DHW
thermostat (3061)
Used / Not used Not used
When Used is
selected, select from
Solar panel and DHW
thermostat
Solar panel
Room temperature
calibration
Disinfection (3041,
3042, 3043)
On
/
Off On
Interval (3042)
Sun / Mon / Tue / Wed
/ Thu / Fri / Sat
Fri
Start time (3043) Set time
(*2)
Water Law settings
WL type (2041)
Water Law 1 /
Water Law 2
Water Law 1
Max outdoor
temperature (2011)
Min outdoor
temperature (2012)
Max water out temp
for Water Law 1 (2021)
(*2)