Field Setting Mode
Disinfection Function
1) "Booster heater" Disinfection
The FSV #3041 should be set to "1 (On)" (Default) to use disinfection function.


[Time variation control of Heat pump and booster heater of DHW]
t
00.00 01.00 22.00 23.00 24.00
T
U
T
H
#3043
#3045
#3044
2) "R290 Heat Pump" Disinfection
The FSV #3041 should be set to "1 (On)" (Default) to use disinfection function.
When FSV#3031 is set to "0(Off)", the disinfection function is only performed by the heat pump to reach a
target tank temp.


[Time variation control of Heat pump and booster heater of DHW]
t
00.00 01.00 13:00 14:00 15:00
T
U
T
H
60
#3043
60min