Appendix _45
Appendix
Appendix
TEMPERATURE TABLE
Available operation range
Mode
Target temperature
Display
Setting range
Current
display
Setting
method
Control
method
Set
View
Default
Available
Cooling
Leaving water
O
O
6~25˚C
• Min : 5~18˚C
• Max : 18~25˚C
-50~94˚C
Up/Down
Hydro or
Indoor unit
Room
O
O
18~30˚C
• Min : 18~22˚C
• Max : 24~30˚C
-50~94˚C
Up/Down
Indoor unit
Heating
Leaving water
O
O
25~55˚C
• Min : 15~37˚C
• Max : 37~55˚C
-50~94˚C
Up/Down
Hydro or
Indoor unit
Room
O
O
16~30˚C
• Min : 16~22˚C
• Max : 24~30˚C
-50~94˚C
Up/Down
Indoor unit
Water
Law
Cooling
Outdoor
X
X
30~40˚C
• Min : 25~35˚C
• Max : 35~45˚C
-50~94˚C
Field
Setting
Mode
SET/VIEW
mode
Hydro unit
or
Thermostat
(Th-1 : Floor,
Th-2 : FCU)
Leaving water
(WL1-Floor)
X
X
25~18˚C
• Min : 18~25˚C
• Max : 5~18˚C
-50~94˚C
Leaving water
(WL2-FCU)
X
X
18~5˚C
• Min : 18~25˚C
• Max : 5~18˚C
-50~94˚C
Heating
Outdoor
X
X
-10~15˚C
• Min : -20~5˚C
• Max : 10~20˚C
-50~94˚C
Leaving water
(WL1-Floor)
X
X
40~25˚C
• Min : 40~55˚C
• Max : 17~37˚C
-50~94˚C
Leaving water
(WL2-FCU)
X
X
50~35˚C
• Min : 40~55˚C
• Max : 17~37˚C
-50~94˚C
Temperature Shifting
O
X
-5~5˚C
Default
-
Up/Down
Hydro unit
DHW
DHW tank
O
O
40~50˚C
• Min : 30~40˚C
• Max : 50~65˚C
-50~94˚C
Up/Down
Hydro unit
Outdoor temperature
X
O
-
-
-50~94˚C
-
DIP SWITCH SETTING
S/W
OFF (Default)
ON
S/W #1
Heating and Cooling
Heating only
S/W #2
Target temp : Water outlet Temp.
Target temp : Indoor air Temp.
S/W #3
Air sensor in remote controller
External air sensor
S/W #4
No Use
No Use
S/W #5
No Use
No Use
S/W #6
No Use
No Use
S/W #7
No Use
No Use
S/W #8
No Use
No Use