Features & Operation
64
Indoor fan control in the heating mode
6
Indoor fan is controlled depending on the temperature of indoor heat exchanger in the heating mode.
The temperature of indoor heat exchanger Indoor fan speed
below 28°C off
28°C ~ below 34°C LL speed
34°C ~ below 40°C L speed
above 40°C setting speed
The temperature of indoor heat exchanger Indoor fan speed
above 20°C UL speed
below 20°C off
after 10 minutes when compressor stops operating off
When compressor is on
40°C
34°C
28°C
20°C
Setting speed
L speed
LL speed
OFF
Compressor
OFF OFF
UL
ON
When compressor is off
INDOOR FAN CONTROL
◆ When compressor begins operating
◆ When compressor stops operating