Features & Operation
;It carries out cooling or heating automatically after detecting the room temperature
◆ Operating pattern
room temperature(ºC) ∆T=-2, -1, 0, 1, 2ºC
◆ Operating specification
room temperature ≥ 21ºC+∆T, The unit is operated in the Cool mode.
room temperature < 21ºC+∆T, The unit is operated in the Heat mode.
Auto Operation
1
Cooling Operation
2
4-2 INVERTER
Room Temp ≥ 21ºC+∆T
Room Temp < 21ºC+∆T
Cooling : Ts=24ºC + ∆T
Heating : Ts=24ºC + ∆T
◆ Operating pattern
room temperature(ºC) TS=Remocon setting temp.
◆ Operation specification
- Compressor on : Room temp. = Setting temp(Ts)+1ºC
- Compressor off : Room temp. = Setting temp(Ts)
- The fan speed of indoor unit follows the setting volume of remote control