Defrost operation is controlled by sensing the temperature of outdoor unit’s heat exchanger
and temperature of outdoor and accumulating time of compressor operation.
How to sense defrost conditions
A
condition
Outdoor heat exchanger operates under L1 line for over 120Mminutes.
B condition
When operating time of compressor without stopping for over 35minutes.
C condition
Outdoor heat exchanger operates under L2 line for over 3minutes
Defrost operation conditions
A condition
B
C condition
Defrost absolution conditions
- If the temperature of outdoor heat exchanger is over 20ºC.
- When defrost operation time is over 12 minutes.
Operating pattern
Detrost Control in heatmode