CW-6300 Series
17
<7> Specifications
CW- 6300 Series
Note: the cooling capacity is under 30 water temperature and 40 ambient
temperature working conditions with standard voltage.
The max. pump flow is obtained by testing the pump individually on test criteria
GB/T 3216-2005.criteria GB/T 3216-2005.
Model
CW-6300AN
CW-6300BN
CW-6300EN
Voltage
AC 1P 220V
AC 1P 220V
AC 3P 380V
Frequency
50Hz
60Hz
50Hz
Current
3.4~21A
3.4~21A
2.5~9A
Compressor
power
2.76KW
2.70KW
2.65KW
3.76HP
3.67HP
3.61HP
Nominal cooling
capacity
27808Btu/h
27842Btu/h
27432Btu/h
8.15KW
8.16KW
8.04KW
7007Kcal/h
7016Kcal/h
6913Kcal/h
Refrigerant
R-22 / R-410a
Refrigerant
charge
2150g
2100g
2350g
Precision
±1
Reducer
Capillary
Protection
Overcurrent protection for compressor, flow alarm, over temperature alarm
Pump power
0.37~1.1KW
Tank capacity
45L
Inlet and outlet
Rp 1’’
Max. lift
28~53 M
Max. flow
70 ~116 L/min
N.W
165Kgs
G.W
210Kgs
Dimension
83 X 65 X 117 cm (L X W X H)
Package
dimension
111 X85 X 140 cm (L X W X H)