EasyManua.ls Logo

Sanyo C2462R - Page 40

Sanyo C2462R
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 40 –
SM830092
2) Air Conditioner does not Operate
1
Circuit breaker trips (or fuse blows).
(a) When the circuit breaker is set to ON, it is tripped soon.
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 2 M or less, it is a defect of insulation.
1
2
3
(Example)
*Set the circuit breaker to OFF.
Remove power supply cords
from the terminal plate in
the outdoor unit.
• Check insulation resistance
of power supply cords.
OK
NO
NO Insulation of
outdoor unit
is defective.
Execute
rewiring.
Remove inter-unit power line
from the terminal plate in
the outdoor unit.
• Check insulation resistance
of outdoor unit.
OK
Remove inter-unit power line
from the terminal plate in
the indoor unit.
• Check insulation resistance
of indoor unit.
OK
Inter-unit power lines are
defective.
NO
Insulation of
outdoor unit
is defective.
• Check insulation
resistance of
electrical parts
in the outdoor unit.
• Check insulation
resistance of
electrical parts
in the indoor unit.
Execute
rewiring.
1032_X_S
+
+
+
+
+
+
1 3
2
Circuit
breaker
Power
supply
cords
Inter-unit
power line
Outdoor
unit
Indoor
unit
Ground
+
+
4
1
2
G
L1
L2
G
4
1
2
G
4
12. SERVICE PROCEDURES

Related product manuals