EasyManua.ls Logo

Sanyo CH3642 - Page 169

Sanyo CH3642
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
2
3
4
Section
IV - 13
SM830082
4. Service procedures
9) Symptom: LCD on the remote controller displays “CHECK P01”. (Indoor fan protection
thermostat operation warning)
No
No
Yes
Yes
Yes
2098_THS_I
Start
Is there 230-208 V AC between T20-1
and T20-3 on the indoor unit PCB?
Is the indoor fan wire winding
protection thermostat (49FI) off?
Replace the indoor fan.
Correct the connection
Replace the indoor unit PCB.

Table of Contents

Related product manuals