EasyManua.ls Logo

Sanyo CH3642 - Page 171

Sanyo CH3642
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
2
3
4
Section
IV - 15
SM830082
4. Service procedures
11) Symptoms: LCD on the remote controller displays “CHECK P03”.
(Alarm for unusual discharge temp. of compressor)
12) Symptom: LCD on the remote controller displays “CHECK P04”. (High-pressure switch
activation warning)
0343_M_I
Start
Unusual discharge gas temperature
• Refrigerant shortage
• Clogged refrigerant circuit
• Electronic refrigerant control
valve defect (indoor unit)
No Yes
No
Yes
0344_M_I
Start
Are there connection defects in
the wiring?
High-pressure switch defect
Repair the wiring.
The system does not operate again.
High-pressure switch activation
(Both cooling and heating)
• Electronic
refrigerant
control valve
defect
Refrigerant
over-charged
(Cooling)
• Outdoor unit, heat exchanger dirty,
clogged
• Outdoor unit air short
• Outdoor fan stopped
(Heating)
• Outdoor unit air short
• Indoor unit, heat exchanger dirty,
clogged
• Large pipe side service valve
closed
• Indoor fan stop
• Air filter clogged

Table of Contents

Related product manuals