Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 240V Single phase 50Hz
Rating Conditions Running Amps. A 0.330 0.660 12.01 13.0
Power Input kW 0.072 0.146 2.882 3.10
Full Load Conditions Running Amps. A 0.330 0.660 14.51 15.5
Power Input kW 0.072 0.146 3.472 3.69
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.