Sanyo SAP–K302A - Compressor Not Operating; Flap Motor Not Operating; Outdoor Fan Speed Control Issues

Sanyo SAP–K302A
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-3-3. Only compressor does not run.
9-3-4. Only flap motor does not run.
9-3-5. Function of outdoor fan speed control does not work properly.
Refer to "8-4. Outdoor Fan Speed Control".
Check outdoor PCB Ass'y.
Check air sensor in outdoor unit.
Measure resistance of flap
motor winding.
(FLP)
Check compressor motor
capacitor.
Measure resistance of
compressor motor winding.
Measure resistance of power
relay. (PR)
NO
NO
YES
YES
Refrigerant gas shortage. Charge refrigerant gas (R22).
Rotor may be locked up.
(C1 or C2)
Measure Power supply
voltage.
The voltage is too low.
No
Compressor internal protector
is working.
Temperature of compressor
is abnormally high.
28