26
6. ELECTRICAL DATA
6-1. Electrical Characteristics
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 – 240V Single phase 50Hz
Rating Conditions Running Amps. A 0.13 / 0.14 0.24 / 0.25 3.23 / 3.21 3.6 / 3.6
Power Input kW 0.026 / 0.031 0.052 / 0.060 0.692 / 0.719 0.77 / 0.81
Full Load Conditions Running Amps. A 0.13 / 0.14 0.24 / 0.25 4.13 / 4.01 4.5 / 4.4
Power Input kW 0.026 / 0.031 0.052 / 0.060 0.892 / 0.919 0.97 / 1.01
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 – 240V Single phase 50Hz
Rating Conditions Running Amps. A 0.13 / 0.14 0.24 / 0.25 2.83 / 2.91 3.2 / 3.3
Power Input kW 0.026 / 0.031 0.052 / 0.060 0.602 / 0.649 0.68 / 0.74
Full Load Conditions Running Amps. A 0.13 / 0.14 0.24 / 0.25 4.03 / 3.91 4.4 / 4.3
Power Input kW 0.026 / 0.031 0.052 / 0.060 0.822 / 0.869 0.90 / 0.96
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
Indoor Unit SAPK71GJHA
Outdoor Unit SAPC71GHA

Table of Contents