EasyManua.ls Logo

Sanyo SAP-K71GJHA - Air conditioner does not operate

Sanyo SAP-K71GJHA
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-2. Air conditioner does not operate.
9-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 2M or less, insulation is defective (“NO”).
Measure insulation
resistance of electrical
parts in outdoor unit.
NO
NO
Set circuit breaker to OFF.
*
Measure insulation
resistance of electrical
parts in indoor unit.
1
Remove both power supply wires
and inter-unit wires from terminal
plate in outdoor unit.
Measure insulation resistance
of outdoor unit.
2
Remove inter-unit wires from
terminal plate in indoor unit.
Measure insulation resistance
of indoor unit.
Insulation of
outdoor unit
is defective.
Insulation of
indoor unit
is defective.
WARNING
11
2
8
92
3
44
55
66
77
Indoor
unit
2
Outdoor
unit
1 1
Inter–unit
wiring
Power
supply
wiring
Circuit
breaker
Power
supply
Ground
45

Table of Contents

Related product manuals