Power Source 220–240V Single phase 50Hz
Voltage rating 220/230/240 V
Performance Cooling Heating
Capacity kW 2.05 / 2.05 / 2.05 2.50 / 2.50 / 2.55
BTU/h 7,000 / 7,000 / 7,000 8,500 / 8,500 / 8,700
Air circulation (High)
Moisture removal (High) Liters/h 0.56 —
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264
Running amperes A 3.6 / 3.6 / 3.6 3.2 / 3.2 / 3.3
Power input W 770 / 790 / 810 680 / 710 / 740
Power factor % 97 / 95 / 94 97 / 96 / 93
C.O.P. W/W 2.66 / 2.59 / 2.53 3.68 / 3.52 / 3.45
Compressor locked rotor amperes A 17 / 18 / 19 17 / 18 / 19
Features
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer 1-hour OFF / 12-hours ON or OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R22 / 850
Refrigerant control Capillary tube
Operation sound Indoor : Hi / Me / Lo dB-A 38 / 34 / 31 38 / 34 / 31
Outdoor : Hi dB-A 46 46
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant Narrow tube mm (in.) 6.35(1/4)
tube diameter Wide tube mm (in.) 9.52(3/8)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Dimensions & Weight
Remarks:
Rating conditions are:
Cooling : Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating : Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.