Heating
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the
controller in the indoor unit.
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 5
minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant
pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor
operation.
Thermo. ON : When the room temperature is below T – 1°C (T°C is set temperature).
Compressor
ON
Thermo. OFF : When the room temperature is equal to or above set temperature T°C.
Compressor
OFF
*1: Refer to "8-6 Cold Draft Prevention".
NOTE
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes
5 minutes 5 minutes
ON OFF ONOFFCompressor OFF
ON OFF ONOFFOutdoor fan OFF
Set speed
LL
LL
ON
OFF
OFF OFF ON OFF ON
*1
OFF
OFF
ON
ON
i
Reversing cycle
j
Thermo.
ON
Thermo.
OFF
Thermo.
ON
Thermo.
OFF
More than
5 minutes
Signal from remote control unit
T °C
T–1 °C
T–2 °C
set temp.
Indoor fan
Standby lamp
Indoor heat exch.
coil temp.
34°C
Solenoid coil
(4 way valve)
Operation button
Room temp.
*1
Set speed
30 seconds30 seconds
Max. 10minutes
OFF
37