Heating
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the
controller in the indoor unit.
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 5
minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant
pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor
operation.
Thermo. ON : When the room temperature is below T – 1°C (T°C is set temperature).
Compressor
ON
Thermo. OFF : When the room temperature is equal to or above set temperature T°C.
Compressor
OFF
1: Refer to 10-5 "Cold Draft Prevention".
22
Set temp.
Signal from remote control unit
Outdoor fan
Compressor
ONON OFF OFF
OFFOFF
T°C
T–1°C
T–2°C
Room temp.
Thermo.
ON
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes
Thermo.
OFF
Thermo.
ON
Thermo.
OFF
ONON
5 minutes
OFF
OFF
ON (Reversing cycle)
OFF
LL LLOFF
OFF
Set speed
30 seconds
LL
30 seconds
LL
*
1
OFF
*
1
ON
OFF
ON
OFF
OFF
Indoor fan
Standby
lamp
Indoor heat
exch. coil
temp. 35°C
Solenoid coil
(4-way valve)
Operation
button
5 minutes
*
1
25°C
20°C
More than
5 minutes
ON
Set speed
ON
NOTE