11-2-3.Only outdoor unit does not run.
A. Check setting temperature.
B. Check PCB Ass'y in either indoor or outdoor unit.
11-2-4.Only indoor unit does not run.
OK
NO
Is room temperature too low ?
Try to lower setting temperature by
temperature setting button cooler.
Outdoor unit still does
not run.
Remote control unit is defective.
Try to run using another remote
control unit.
COOL
OK
NO
Is room temperature too high ?
Try to raise setting temperature by
temperature setting button warmer.
Outdoor unit still does
not run.
Remote control unit is defective.
Try to run using another remote
control unit.
HEAT
Indoor PCB Ass'y is defective.
Check voltage between terminals
No. 3(+) and No. 4 at terminal plate.
(DC 24V)
No voltage appears.
Outdoor PCB Ass'y is defective.
OK
Indoor PCB Ass'y is defective.