35
11-4. Air conditioner operates, but abnormalities are observed.
11-4-1.Operation does not switch from HEAT to COOL (or COOL to HEAT).
Indoor PCB Ass'y is defective.
Check voltage between terminals
No. 3(+) and No. 5 at terminal plate.
(DC 24V)
No voltage appears.
Outdoor PCB Ass'y is defective.
OK
Remote control unit may be defective.
Measure resistance of 4–way valve's
winding.
Receiver in switch Ass'y may be
defective.
COOL HEAT
Check voltage between terminals
No. 3(+) and No. 5 at terminal plate.
(0V)
HEAT COOL
If unit A is stopped, unit B will switch to cooling or drying operation.
(Example) Unit A in heating mode
Unit B in cooling or drying mode
Unit A in heating mode
(Heating operation takes precedence.)
Unit B fan operating
• If the units are operated in different modes (for example, unit A in the heating mode and unit B in the cooling or
drying mode), the results are as follows.
Units A and B cannot be operated in different modes simultaneously (for example,
unit A operating in the heating mode while unit B is operating in the cooling or
drying mode). When operating two units at the same time, set them both to the
same mode. Note however that though technically different modes, unit A can
operate in the cooling mode while B is operating in the drying mode.
CAUTION