3.6 Exception Responses
The instrument sends an exception response when errors are detected in the received message. To
indicate that the response is notification of an error, the high order bit of the function code is set to 1.
Exception Response
Instrument
Address
Function (high
order bit is set to 1)
Exception
Code
Error Check
1 byte 1 byte 1 byte 2 byte
Exception response codes:
01 - Illegal function
02 - Illegal data address
03 - Illegal data value
06 - Busy, rejected message. The message was received without errors, but the instrument is being
programmed from the keypad (only for requests accessing setup registers).
NOTE When the character framing, parity, or redundancy check detects a communication error,
processing of the master's request stops. The instrument will not act on or respond to the message.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec PM130EH SERIES and is the answer not in the manual?

Satec PM130EH SERIES Specifications

General IconGeneral
DisplayLCD
Frequency50/60 Hz
CommunicationRS-485, Modbus RTU
Digital Outputs2 relay outputs
Data LoggingYes
Measurement TypePower, Energy, Harmonics
Current Input1A or 5A
MountingPanel Mount
Power Supply85-265V AC/DC
Digital Inputs2
Analog OutputsUp to 4
Operating Temperature-20 to 70°C
Dimensions96 x 96 mm
Weight0.5kg