EasyManua.ls Logo

SCADAmetrics EtherMeter - Mechanical, Electrical, and Environmental Specifications; Auxiliary Inputs and Outputs; Standards and Regulatory Compliances

SCADAmetrics EtherMeter
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
D. Mechanical/Electrical/Environmental
Dimensions: 8.25” x 4.75” x 1.75”
Weight: 13.5 Ounces
Temperature Range: -20C to +70C
Relative Humidity: 5% to 95%, Non-Condensing
Panel Mounts: Two (2) Universal Din-Rail Clips
LCD Display: 2x16 Character, Backlit
Supply Voltage: 9 VDC to 36 VDC
Supply Current: 275 mA Max. (2.50 W Max.)
Nominal: 85 mA @ 24 VDC,
Nominal: 62 mA @ 24 VDC w/ Backlight OFF
Terminal Block Conductors: 16AWG Max, 26AWG Min.
Internal Power Efficiency: 76%, Typical
Circuit Protection: Fused (1000mA) + 9 TVSS Diodes
Environmental: ROHS-Compliant, Lead-free
E. Auxiliary Inputs/Outputs
Analog Inputs: Two 4-20mA Inputs (9.6 bit A/D),
240 Ohm Loop Resistance
Configurable as 0-5VDC (10bit A/D)
Aux Digital I/O: Two (2):
One (1) Digital Output
One (1) Configurable As Digital Input or Output
Output(s): TTL (0-5VDC) Output
Input(s): TTL Dry-Contact Input
MODBUS Fn. Codes: 01 - Read Coil Status,
02 - Read Input Status,
03 - Read Holding Registers,
04 - Read Input Registers,
05 - Force Single Coil
15 - Force Multiple Coils
DF1 Codes: Protected Typed Logical Read With 3 Address Fields
Protected Typed Logical Write With 3 Address Fields
ADAM-4000 Fn. Codes: #AAn - Read Analog Inputs,
(ADAM-Version Only) $AA6 - Read Discrete Inputs,
#AA1n0d - Write Discrete Outputs,
$AAM - Read Device ID
F. Standards And Regulatory Compliances
Safety (US): UL 60950-1 Recognition (MET Labs File No. E112874)
Safety (Canada): CSA C22.2 No. 60950-1 Recognition (MET Labs File No. E112874)
Emissions (US): FCC Part 15, Class A
Emissions (Canada): ICES-003
Meter Interface: AWWA C707-05
Environmental: ROHS-Compliant, Lead-Free
Manufacturing Location: USA