4
3 SPECIFICATIONS
A. Meter Communications
Protocols: Sensus Variable-Length: 4 to 8 Digit
Sensus Fixed-Length: 4 to 6 Digit
Neptune E-Coder Plus: 8 digit
Neptune ProRead Basic: 3 to 6 digit
K-Frame (Elster-AMCO, ABB, Kent): 6 Digit
Pulse (Dry Contact) Output, 60 Hz Max.
Protocol Recognition: Encoder Auto-Detect
Flow Rate Calculation: dV/dT (Fixed dT or Fixed dV)
Touch-Read Compatibility: Yes, when optional filter installed.
(See Touch-Read Compatibility Matrix.)
B. Serial Communications
Ports: RS-232C (EIA-561 Jack)
RS-485 (Phoenix Terminal)
Speed: 300 to 115200 bps
Port Parameters: 8N1, 7E1, 7O1, 7N2
Handshaking: Fixed RTS, Null Modem,
RTS/CTS, CD-Collision Avoidance,
None
Industrial Protocols: MODBUS/RTU,
MODBUS/ASCII,
DF1/FULL-DUPLEX,
DF1/RADIO-MODEM,
RAW-ASCII (ASCII-Version Only),
ADAM-4000 (ADAM-Version Only)
REMOTE VFDisplay (VFDisplay-Version Only)
Setup Terminal: ANSI, 25x80 char, 9600, 8N1
C. Ethernet Communications
Speed: 10 Mbps (10BaseT)
Addressing: DHCP or Static IP
Web Server: Yes
Ping Server: Yes
Industrial Protocols: MODBUS/TCP (4 Sockets),
EtherNet/IP,PCCC-Encapsulation (4 Sockets),
MODBUS/UDP
MAC ID: IEEE-Assigned OUI: 00-1D-C8