Floor Protection requirements:
The floor protector must extend completely beneath the stove and to the front, sides and rear as
indicated below. The floor protection needs only to be a standard ember protection.
USA:
For USA the protected area must cover the floor completely under the stove and extend 16" to the
front of the fuel door opening and 8" beyond either sides of the fuel door opening
Canada:
For Canada the protected area must cover the floor completely under the stove and extend 18" to the
front of the fuel door opening and 8" beyond both sides and the back of the stove.
Parallel installation:
A B C D E F
USA 16" 3" 8" 40 ¼” 39 ½”
Canada 450 203 203 1276 1283