3.13 Relay module
3.13.1 1.13.1 General description
If the PROTECT-PSC is in mode 3, then the output module acts like a module with
2x2 relay outputs.
The relay outputs must be opened at least once per year. This can be done manu-
ally by actuating the protective device on the input side or automatically in the user
program.
The relay outputs must be fused by means of an appropriately dimensioned fuse
(max. 4A slow blowing).
3.13.2 PSC-S-Relais
Technical data