Overview|Buttons and LED in the event of an alarm
B-HB-0133EN Operating panel Integral MAP|User manual 9
3.2.3 Exploration/intervention function
(Depends on programming; delay function must be activated)
If an alarm is received with the delay layer activated, the beep acknowledgement time
sounds and the LED next to the button Intervention
C
flashes. Pressing the button
Intervention
C
within the acknowledgement time activates the intervention/interven-
tion mode. The LED next to the button lights up and the signal tone changes from ac-
knowledgement time to intervention/intervention mode. The activation of the main de-
tector output is delayed by the programmed intervention time.
Pressing and holding the button Intervention
C
within the intervention time shows the
remaining intervention time on the display.
Further Information: Chapter Activate exploration/intervention function, Page17
3.2.4 Reset alarm/fault signal
Pressing the button Buzzer silenced
D
disables the signal tone of an active alarm or
fault message in the fire alarm control panel; the LED remain lit up. Any additional alarm
or fault message will trigger the alarm and fault signal tones again. Acknowledgement
and intervention signal tones cannot be reset.