Detailed Application Examples
Job Done Example 2
4.4
Use the following settings to configure Port 9 of the
SEL-2030 and perform Autoconfiguration during the port
setting process:
DEVICE=S
CONFIG=Y
PORTID=(set automatically by autoconfiguration
process)
BAUD=19200
DATABIT=8 STOPBIT=1 PARITY=N
RTS_CTS=N XON_XOF=N
TIMEOUT=5.0
Use the following settings to configure Port 12 of the
SEL-2030:
PORT:12
DEVICE=M
PROTOCOL=S
FAST_OP=N
PORTID="SEL-2890 Port"
MODEM=N
BAUD=19200
DATABIT=8 STOPBIT=1 PARITY=N
RTS_CTS=Y XON_XOFF=N
TIMEOUT=5.0 ECHO=Y
AUTO_HELP=Y
TERTIME1=1
TERSTRING="\004"
TERTIME2=OFF
Use the settings below to configure the SEL-2890:
PORT=23
TEL_PROC=Y
TUNNEL=N
UDDELAY=2
MTDELAY=0.8
WEB=SEL
DHCP=N
DNS_IP=192.168.0.1
DOMAIN=
HOST_NAME=
EMAIL=N
ROUTE=N
SPEED=19200
STOP=1
PARITY=NONE
FLOW=HARDWARE
IP=192.168.0.100

Table of Contents