2.2. Technical specifications
Range / Generating set type RENTAL POWER / R570U
Weights and Dimensions
Dimensions with standard tank
Dimensions l x w x h:
5031 mm x 1560 mm x 2695 mm
Weight:
4870 kg dry weight 5410 kg in operating configuration
Hood:
M228C
Noise level:
85 dB à 1 m (0.70)
75 dB à 7 m (0.70)
Dimensions with high autonomy tank
Dimensions l x w x h:
5083 mm x 1560 mm x 2780 mm
Weight:
5590 kg dry weight 7240 kg in operating configuration
Hood:
M228C-DW
Noise level
:
85 dB à 1 m (0.70)
75 dB à 7 m (0.70))
Output
Voltage* Hz Phase Load factor
Max current (A)
Emergency
Emergency power
kW / kVA
Prime power
kW / kVA
480/277 V 60 3 0.8 758 504 / 630 458.2 / 572.7
*Available :
• 380 / 220 V ;
• 220 / 127 V ;
• 208 / 120 V.
(1) ESP: Stand-by output available for emergency use under variable charge up to 200hrs per year as per lSO 8528-1, no overload
available under these service conditions.
(2) PRP: Main output available continuously under variable load for an unlimited time period per year as per ISO 8528-1, an overload
of 10% one hour every 12 hours is available, as per ISO3046-1.
Engine data
Manufacturer / model VOLVO TAD1641GE
Type Turbo
Cylinder configuration 6 x L
Cubic capacity 16.12 L
Rotation speed 1800 Tr/min
Max emergency/prime power at nominal speed 565 / 504 kW
Adjustment type Electronique
Fuel consumption
110 % (emergency power) 137.97 L/h
100 % main power 120.73 L/h
75 % main power 88.79 L/h
50 % main power 59.78 L/h