EasyManuals Logo

Secure PT3 Series User Manual

Secure PT3 Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
Page 10 of 40
BGX701-014-R03, User Manual for PT3 Transducers
Public
5 Technical specifications
Environmental and safety specifications
Protection class
II (double insulation) EN 61010-1
Pollution degree
2
Ingress protection
Protection enclosure - IP 40, terminals and USB - IP 20
(EN 60529)
Temperature
Operating range -5
°
C to + 55
°
C
Limit range for
storage
-25
°
C to +70
°
C
Limit range for
transportation
-25
°
C to +70
°
C
Temperature
coefficient
± 0.1% / 10
°
C
Reference conditions
Usage group (IEC
60688)
Group I
Reference
temperature range
+10
°
C to + 35
°
C
Pre-conditioning 30 minutes
Environment
Indoor only
Humidity
95% non-condensing
Altitude level
Up to 2000 m
Over voltage / Installation category
CAT III for 300 VAC and CAT II for 600 VAC
Measurement category
CAT III for 300 VAC and CAT II for 600 VAC
Insulation AC voltage test (IEC 61010:2010)
3.7kV
Impulse voltage test (IEC 61010:2010)
6.4kV
Electrical specifications
Transducer variant
Parameter Specification
AC voltage
Input voltage (U
n
)
100 V to 500 V
(L-L)
Measuring range
0 to 130% U
n
Scale factor 0.8 to 1.5 of U
n
(up to 500 V)
Frequency 50/60 Hz (±5%)
Maximum overload voltage 1.3 x U
n
continuously
2 x U
n
for 1 second, with up to 10 repetitions at 10 second
intervals
Output curve mA
type
0-20 mA, 4-20 mA and 0-10 mA
(Applicable for accuracy class 1.0, 0.5 and 0.2)
0-5 mA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secure PT3 Series and is the answer not in the manual?

Secure PT3 Series Specifications

General IconGeneral
BrandSecure
ModelPT3 Series
CategoryTransducer
LanguageEnglish