I>>> . Reset Mode [Protection Para / I>>>]
instantaneous If: I>>> . Char = DEFT
• instantaneous, denite time•
If: I>>> . Char = IEC NINV
• instantaneous, denite time, inverse time•
If: I>>> . Char = IEC VINV
•
instantaneous, denite time, inverse time
•
If: I>>> . Char = IEC EINV
•
instantaneous, denite time, inverse time
•
If: I>>> . Char = IEC LINV
• instantaneous, denite time, inverse time•
If: I>>> . Char = RINV
•
instantaneous, denite time, inverse time
•
If: I>>> . Char = HV Fuse
• instantaneous, denite time•
If: I>>> . Char = FR Fuse
•
instantaneous, denite time
•
If: I>>> . Char = IEEE MINV
•
instantaneous, denite time, inverse time
•
If: I>>> . Char = IEEE VINV
•
instantaneous, denite time, inverse time
•
If: I>>> . Char = IEEE EINV
•
instantaneous, denite time, inverse time
•
If: I>>> . Char = EF Curve
•
instantaneous, denite time
•
╚═▷ Reset Mode
P.1
Reset Mode
I>>> . tReset [Protection Para / I>>>]
0.1s
Only available if:
• I>>> . Reset Mode = denite time•
0.00s . . . 60.00s P.1
Reset delay for intermittent phase failures (INV characteristics only)
67WIC1WIC1-2.0-EN-REF
9 Protection Parameter
9.10.2 I>>>: Settings