User Manual
IEC 61850 MODBUS
GATEWAYS
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
MI00705-0-EN
WEB SERVER PORT (default: 80)
Sets the communication port for the web server.
IP CHANGE FROM DISCOVERY (default: Enabled)
Selects whether or not the device accepts the IP address change from the Seneca Discovery Device software.
TLS (default: Disabled)
Enables or disables cryptographic protocols via TLS.
MODBUS TCP-IP CLIENT
Enables or not the TCP-IP client Modbus
MODBUS TCP-IP SERVER#1…3 PORT
Sets the port for the max 3 remote TCP-IP Modbus servers
MODBUS TCP-IP SERVER#1…3 ADDRESS
Sets the IP address for the max 3 remote TCP-IP Modbus servers
MODBUS TCP-IP CLIENT TIMEOUT [ms]
Sets the timeout for remote TCP-IP Modbus servers
MODBUS TCP-IP CLIENT WRITING ATTEMPTS
Selects the number of writing attempts to be made on a remote TCP-IP Modbus server before returning an error
and activating the quarantine.
MODBUS TCP-IP CLIENT MAX READ NUM
Sets the maximum number of simultaneous reading ModBUS registers of the remote TCP-IP Modbus server,
the firmware will use this value to optimize the ModBUS readings.
MODBUS TCP-IP CLIENT MAX WRITE NUM
Sets the maximum number of simultaneous writing ModBUS registers of the remote TCP-IP Modbus server, the
firmware will use this value to optimize the ModBUS writings.
SERVER AFTER FAIL DELAY
Sets the number of quarantine seconds after a tag has been declared in fail (i.e. these tags are no longer
considered) before being interrogated again.
STOP MODBUS READING WHEN NO IEC61850 CONNECTION
If active, it allows to stop the modbus communication when the communication with the IEC61850 client is lost.
This allows to trigger any timeouts present in the modbus slave/server devices.