18
FILTER >
1S
Sets the time parameter for averaging input values, There
are 8 Options: 1S, 2S, 5S, 8S, 10S, 20S, 40S, and 60S.
Note: Larger filter values mean more stable displays but
longer response times. Please consider your system
safety requirements.
LOOP ADJUST 4mA >
3.75
Adjusts the minimum current output to match the external
current measurement. Adjustable from 3.70 mA to 5.00 mA.
LOOP ADJUST 20mA >
21.00
Adjusts the maximum current output to match the external
current measurement. Adjustable from 19.00 mA to 21.00
mA.
TEST 4~20mA
OUTPUT
Press the UP and DOWN arrow keys to manually select any
output current value from 3.7 mA to 21.00 mA to test the
current loop output. The value changes 0.01mA each time
the UP/DOWN key is pressed. If the UP/DOWN key is
pressed and held for more than 5 seconds, The value will be
adjusted by 0.1mA continuously.
TEST OC
OUTPUT
Press the UP and DOWN arrow keys to manually select the
state of the open collector output.
PASSWORD MENU
OFF
Selects whether or not the password is needed to enter the
Main Menu. Note: the password is input by pressing the
RIGHT-DOWN-UP-DOWN arrow keys in sequence and
cannot be changed.
RESTORE FACTORY SETTINGS>
Restores factory settings. In order to do so, you must enter
the correct key code. The key code is input by pressing the
RIGHT-DOWN-UP-DOWN arrow keys in sequence.