THE PRESSURE AT THE GAS CONTROL VALVE SHALL NOT EXCEED
1/2 PSI.
Never supply the appliance with a gas other than the one that is indicated on the
data plate. Using the incorrect gas type will cause improper operation and could
result in serious injury or death. If you need to convert the appliance to another
type of fuel, contact the dealer your purchased it from.
Never use an adapter to make a smaller gas supply line t the cooker connection.
This may not allow the correct amount of gas ow for optimum burner
operation,resulting in poor cooker performance.
WARNING
IMPORTANT
10
2.4.1 Gas Supply to the Appliance
2.4.2 Quick Disconnect Connection
A properly sized and installed gas line will deliver a supply pressure between
7.0" W.C. (17.4 mbars, 1.74 kPa) and 10.0" W.C. (24.9 mbars, 2.49 kPa) natural gas or
between 11.0" W.C. (27.4 mbars, 2.74 kPa) and 13.0" W.C. (32.4 mbars, 3.25 kPa) for
propane to all appliances connected to the supply line, operating simultaneously at
full demand.
02. EQUIPMENT INSTALLATION
In North America, gas appliances equipped with casters must be installed with
connectors that comply with the Standard for Connectors for Movable Gas Appliances,
ANSI Z21.69.CSA 6.16 Latest Edition. This connection should include a quick
disconnect device that complies with the Standard for Quick Disconnect Devices
for Use With Gas Fuel Appliances ANSI Z21.41.CSA 6.9 Latest Edition.