Operating Instructions – Explosion-Proof AC Motors DR63/eDR63, DVE250/280
7
Parameter setting: Frequency inverters for category 3 motors
Startup
Maximum speed The maximum motor speed must be limited in the "System limits" window. Observe the
following when you set the parameter maximum speed:
Maximum speed motor limit speed and
Maximum speed maximum gear unit input speed n
emax
(see gear unit nameplate)
Automatic
adjustment
The parameter automatic adjustment is activated via guided startup. Thus, the fre-
quency inverter sets parameter IxR value with each enable signal. A manual change is
not permitted.
7.3.2 Startup procedure for MOVIDRIVE
®
B
Observe the following points during startup:
Use the MOVITOOLS
®
MotionStudio software, version 5.70 or higher, for a guided
startup procedure.
Startup and operation of the motors of category 3 is possible in parameter sets 1 and
2.
The first startup must always be a complete startup.
The motor configuration only allows for individual drives. You can set either "V/f" or
"vector-controlled" for the control mode.
Select the proper motor series in the "Motor type" window.
In the "SEW motor type 1" window, choose the device category, the nominal motor
voltage, the nominal motor frequency and the line voltage in addition to the motor.
For the application options, you can only select "speed control" and the "hoist" func-
tion. Do not use the options "DC braking" or "Flying start function".
Current limit In guided startup, the Current limit parameter is set to 150 % I
NMot
in parameter
window 1. This value must be reduced according to the permitted maximum output
torque at the gear unit M
amax
.
Maximum speed The maximum motor speed must be limited in parameter window 2. Observe the follow-
ing when you set the parameter maximum speed:
Maximum speed motor limit speed and
Maximum speed maximum gear unit input speed n
emax
(see gear unit nameplate)
Automatic
adjustment
The parameter automatic adjustment is activated via guided startup. Thus, the fre-
quency inverter sets parameter IxR value with each enable signal. A manual change is
not permitted.
Always set the operating mode to "4-quadrant operation" (parameters P820/P821).