3
Safety concept
Drive safety functions
Manual – MOVISAFE
®
CSB51A Safety Option
15
3.7.2 SS1(c) – Safe Stop 1 with time control
When the SS1(c) function is active, the inverter brings the motor to a standstill electri-
cally. The drive safety function STO is triggered after a specified, safety-related time.
This drive safety function corresponds to a controlled stop of the drive according to
EN60204-1, stop category 1.
9007201225618443
=
Drive safety function monitoring
=
STO drive safety function active
v =
Speed
t =
Time
t
1
=
Point of time when SS1(c) is activated and motor deceleration is triggered.
t
2
=
Point of time when STO is triggered.
Δt =
Safety-relevant period of time
INFORMATION
• The SS1(c) function does not monitor the stopping of the drive.
• The safety-related period of time Δt allows the drive to come to a stop. In the
event of a fault, the drive does not come to a stop and becomes de-energized at
the time t
2
(STO).
25931075/EN – 04/2019