286
System Manual – MOVITRAC® B
11
Unit information
Service / List of Errors
11 Service / List of Errors
11.1 Unit information
11.1.1 Error memory
The inverter stores the error message in fault memory P080. The inverter does not save
a new fault until the error message has been acknowledged. The local operating panel
shows the most recent error. Whenever double faults occur, the value stored in P080
does not correspond to the value displayed on the operating panel. This is an example
of what happens with F07 DC link overvoltage followed by F34 Ramp timeout.
The inverter stores the following information when a malfunction occurs:
Error occurred
Status of the binary inputs / binary outputs
Operating state of the inverter
Inverter state
Heat sink temperature
Speed
Output current
Active current
Unit utilization
DC link voltage
11.1.2 Switch-off responses
There are 3 switch-off responses depending on the fault:
Immediate stop/malfunction (immediate switch-off with locking)
This fault response causes immediate locking of the output stage with simultaneous
control of the brake output so that an existing brake is applied. The "fault message" is
set and the "ready message" is revoked.
This status can only be exited by an explicit fault reset.
Rapid stop/malfunction (stop with locking)
This error response causes a stop at the set stop ramp (P136 / P146). This fault stop is
subject to time monitoring. If the drive does not reach the start / stop speed within a
specified time period, the unit goes to the fault state, the output stage is inhibited and an
existing brake is applied. The error message F34 Ramp timeout is generated. The orig-
inal fault message is overwritten. If the drive reaches the start/stop speed, the unit goes
to the fault state, the brake is applied and the output stage is inhibited. The "fault mes-
sage" is set and the "ready message" is revoked.
This status can only be exited by an explicit fault reset.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SEW-Eurodrive MOVITRAC B MC07B0003-2B1-4-00 and is the answer not in the manual?

SEW-Eurodrive MOVITRAC B MC07B0003-2B1-4-00 Specifications

General IconGeneral
BrandSEW-Eurodrive
ModelMOVITRAC B MC07B0003-2B1-4-00
CategoryInverter
LanguageEnglish

Related product manuals