16
OUT1
A1
output
Transmission output
Ground
A2 output
EXT.
RESET
A
B
C
5
4
3
9
8
10
1
2
7
6
Insulated
Power
supply
Input
11
12
13
14
15
17
18
19
20
17
Communication
8. Specifications
8.1 Standard specifications
Mounting : Flush
Setting : Input system using membrane sheet key
Display PV display : Red LED 4 digits, character size 18 x 8mm (H x W)
SV display : Green LED 4 digits, character size 12.6 x 6mm (H x W)
Accuracy (Setting and Indication):
Thermocouple : Within
0.2% of each input span 1digit, or within 2 (4 ),
whichever is greater
However R, S inputs, 0 to 200
(400 ): Within 6 (12 )
B input, 0 to 300
(600 ): Accuracy is not guaranteed.
K, J, E, T, N inputs, less than 0
(32 ): Within 0.4% of input span 1digit
RTD : Within
0.1% of each input span 1digit, or
within
1 (2 ), whichever is greater
DC current : Within
0.2% of each input span 1digit
DC voltage : Within
0.2% of each input span 1digit
Input sampling period : 0.25 seconds
Input Thermocouple : K, J, R, S, B, E, T, N, PL-
, C(W/Re5-26), External resistance, 100 or less
(However, B input: External resistance, 40
or less)
RTD : Pt100, JPt100, 3-wire system
Allowable input lead wire resistance (10
or less per wire)
DC current : 0 to 20mA DC, 4 to 20mA DC
Input impedance: 50
[Connect 50
shunt resistor (sold separately) between input terminals.]
Allowable input current: 50mA or less [when shunt resistor (sold separately)
is used]
DC voltage : 0 to 1V DC
Input impedance: 1M
or more
Allowable input voltage: 5V or less
Allowable signal source resistance: 2k
or less
: 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
Input impedance: 100k
or more
Allowable input voltage: 15V or less
Allowable signal source resistance: 100
or less
OUT1 (Limit control output)
Relay contact : 1a1b, Control capacity: 3A 250V AC (resistive load)
1A 250V AC (inductive load cosø=0.4)
Electrical life: 100,000 times
A1 output
Action : ON/OFF action
Hysteresis : 0.1 to 100.0
( ), 1 to 1000 (DC input) (Default: 1.0 )
Output : Relay contact 1a
Control capacity: 3A 250V AC (resistive load)
Electrical life: 100,000 times
Control action
High limit control action, Low limit control action
OUT1 (Limit control output) hysteresis: 0.1 to 100.0
( ), or 1 to 1000 (DC input)
Circuit insulation configuration
A is not insulated from B, and
A is not insulated from C.