Figure 20: Test rod check: Step 1
3.
Then, guide the test rod along the edges of the area to be protected, as indicated
by the arrow, see figure 21.
4. Watch the OSSD LED on the receiver during the check. The OSSD LED on the
receiver should continuously light up red. The OSSD LED must not illuminate
green.
r
Figure 21: Test rod check: Step 3
5.
If one or more deflector mirrors are used, then the test rod should also be guided
slowly through the area to be protected directly in front of the deflector mirrors.
6. Watch the OSSD LED on the receiver during the check. The OSSD LED on the
receiver should continuously light up red. The OSSD LED must not illuminate
green.
PROJECT PLANNING 4
8024467/2019-06-18 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Core Vibes