Example: Isolated connection of OSSD1 and OSSD2
Figure 24: Dual-channel and isolated connection of OSSD1 and OSSD2
Avoiding any potential difference between load and protective device
If y
ou connect loads to the output signal switching devices (safety outputs) that
then also switch if controlled with negative voltage (e.g., electro-mechanical con‐
tactor without reverse polarity protection diode), you must connect the 0 V connec‐
tions of these loads and those of the corresponding protective device individually
and directly to the same 0 V terminal strip. In the event of a fault, this is the only
way to ensure that there can be no potential difference between the 0 V connec‐
tions of the loads and those of the corresponding protective device.
Figure 25: No potential difference between load and protective device
Further topics
"Int
egration in electrical control", page 24
6.2 System connection (M12, 5-pin)
12
3
4
5
Figure 26: System connection (male connector, M12, 5-pin)
6 ELECTRICAL INSTALLATION
40
O P E R A T I N G I N S T R U C T I O N S | deTec4 Core Vibes 8024467/2019-06-18 | SICK
Subject to change without notice