4.4.5 Laser alignment aid
Important information
DANGER
Hazard due to lack of effectiveness of the protective device
The integrated laser alignment aid switches the OSSDs to the OFF state.
b
Make sure that the outputs of the safety light curtain do not have any effect on the
machine when the integrated laser alignment aid is activated.
b
Only use the integrated laser alignment aid to align the safety light curtain.
Prerequisites
A s
witch is connected.
Switch
The switch is mounted in the control cabinet. A relay or a PLC can also be used as a
switch to enable the integrated laser alignment aid to be switched on and off via a con‐
trol panel, for example.
The switch must be connected in accordance with the circuit diagram below.
24 V DC
S
1
In1
0 V DC
In2
s
Figure 23: Switch for the integrated laser alignment aid
S1 c
losed: integrated laser alignment aid is switched on
S1 open: integrated laser alignment aid is switched off
Further topics
"C
onnection of sender and receiver", page 36
PROJECT PLANNING 4