EasyManua.ls Logo

SICK deTec4 Ex - Fault Indicators

SICK deTec4 Ex
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If front screen contamination increases in ongoing operation, the laser alignment aid
s
witches on or the alignment takes longer than 3 seconds, the receiver shows the align‐
ment quality again.
Further topics
"Indication of the alignment quality", page 71
11.2.3 Fault indicators
Overview
In t
he event of a fault, the type of fault is indicated by the LED display on the sender or
receiver.
Sender
Position of LEDs: see "Sender indicators", page 18.
Table 20: Fault indication on the sender
LEDs Possible cause Rectification
STATE Field
O Y
ellow o
Normal operation, no cable
connec
tion between
sender and receiver.
1)
O Y
ellow Ö Red
Failure in the voltage sup‐
pl
y
b
Chec
k the voltage sup‐
ply, see "Technical
data", page 89.
b
Switch the voltage sup‐
ply off and then on
again.
b
If the fault persists,
replace the sender, see
"Ordering information",
page 98.
Ö Y
ellow Ö Red
The sender identified an
int
ernal fault.
b
S
witch the voltage sup‐
ply off and then on
again.
b
If the fault persists,
replace the sender, see
"Ordering information",
page 98.
O Red ÖÖ Yellow/
green
Reset of the configuration
t
o factory settings is acti‐
vated.
Additional information: see
"Factory settings", page 60.
O R
ed Ö Green
The device is in configura‐
t
ion mode following a
change to the configura‐
tion.
Additional information: see
"Configuration mode",
page 62.
Ö Gr
een Ö Red
A problem occurred when
r
esetting the configuration
to factory settings.
b
R
estart configuration,
see "Factory settings",
page 60.
TROUBLESHOOTING 11
8022883/2019-03-07 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Ex
83
Subject to change without notice

Table of Contents