Operating Instructions | SICK 79
Operating Instructions PAC50
8017612/ZAB1/2017-02-14 | PAC50
Subject to change without notice
9 Technical data
Diagnostic output For versions with 2 switching outputs: Switching output 2 can be used as a diagnostic
output. In the event of an error: refer to table 6
Analog output signal Optional, 4 mA to 20 mA/0 V to 10 V. Automatic switchover depending on the connect-
ed load, or permanently adjustable.
Inverted output signals: 20 mA to 4 mA/10 V to 0 V
Load resistance R
A
with current output < 600 Ohm
Load resistance R
A
with voltage output > 3 kOhm
Display LCD with LED backlighting (green/red), can be rotated electronically by 180°
Pressure display: 4 digits, 16 segments
Option of switching between pressure units in the display: bar, MPa, kPa, psi, and inHg
Update: 1,000, 500, 200, and 100 ms (programmable)
Table 7: Features
9.2 Performance
Non-linearity ≤ ± 0.5% of span (Best Fit Straight Line, BFSL) according to IEC 61298-2
Accuracy ≤ ± 1.5% of span
≤ ± 2.0% of span incl. temperature error
(Including non-linearity, hysteresis, zero point and full
scale error (corresponds to error of measurement according to IEC 61298-2))
Non-repeatability ≤ ± 0.2% of span
Rated temperature range 10 °C ... +60 °C
Table 8: Performance