Operating Instructions PBS plus
OPERATING INSTRUCTIONS PBS plus 8024946 | SICK AG
Subject to change without notice
48
5. COMMISSIONING, OPERATION
Menu item Description Parameter Factory setting
AVGD Attenuation (digital display) 0.00 ... 65.00 s 0.20 s
AVG1 / AVG2 Attenuation (switching output 1 / 2) 0.00 ... 65.00 s 0.00 s
AVG3 Attenuation (analog signal) 0.00 ... 65.00 s 0.00 s
UNIT Unit switchover
BAR, mBAR, MPA, KPA, PSI, KGcm (kg/cm²), %
Order-related
0SET
Zero point adjustment / “Auto-zero”
version (max. 3% of the range)
Yes / No
DISM Display value in display mode
ACT = Current system pressure
LOW, HIGH = Min/Max system pressure
OFF = Display off
SP1 / FH1 = Set threshold value
RP1 / FL1 = Set threshold value
SP2 / FH2 = Set threshold value
RP2 / FL2 = Set threshold value
ACT
DISU Update rate (digital display) 1, 2, 5, 10 updates/second 5
DISR Turn display 180° (digital display) Yes / No
DRES Resolution (digital display)
OPT = Optimized (stable measurement value
display with the rounding factor of the last
digit optimized to the measuring range)
FULL = Maximum (nest resolution, an attenu-
ation of the digital display might have to be
set for a stable measurement value display)
OPT
RHL
Delete memory (min/max system
pressure)
Yes / No
PAS Password entry
0000 = No password, password entry digit
by digit
0000
TAG Measurement device name (TAG)
32 selectable characters (A–Z ‚0 ... 9; - ‚EMPTY)
(2 spaces in a row end entry and causes this
and the character behind it to be deleted)
without