Figure 24: Dimensional drawing of “Flat” STR1
ac
tuator
All dimensions in mm.
Figure 25: Dimensional drawing of “Mini” STR1
ac
tuator
All dimensions in mm.
11.3 Response time and release time in a safe series connection
The reaction times are subject to the following parameters:
•
R
esponse time or enable time
•
Number of devices in series connection
Response time (removal of actuator from response range)
R
esponse time for series connection: 40 ms × number of safety switches in series con‐
nection
Enable time (actuator approaching response range)
Release time for series connection: 100 ms × number of safety switches in series con‐
nection
Risk time (error detection time for external faults)
Risk time for series connection: 100 ms +40 ms * (number of safety switches in series
connection -1)
TECHNICAL DATA 11
8018754/12IU/2020-01-30 | SICK O P E R A T I N G I N S T R U C T I O N S | STR1
39