Pin Wire color
1)
Designation Description
7 Blue 0V 0VDC voltage supply
8 Red In 1 OSSD input 1
2)
1)
Applies to the extension cables recommended as accessories.
2)
When used as an individual safety locking device or as the first safety locking device in a cascade: Apply
24VDC (see "Connecting a cascade", page 25).
b
Make sure that the plug connector is tight.
6.3 Device connection (flying lead)
Prerequisites
DANGER
Incorrect connection of the safety locking device
Loss of safety function
b
In the case of insulating material/connection strands, observe the necessary
temperature resistance and mechanical load capability.
b
Only use safe contacts for safety functions.
Prerequisites
•
Mounting is completed.
•
Electrical installation is carried out according to the project planning.
•
Dangerous condition of the machine is and remains off during the electrical instal‐
lation.
•
Outputs of the device have no effect on the machine during electrical installation.
Device connection (flying leads)
Table 3: Cable assignment for device connection
Wire color Designation Description
White Out AUX Application diagnostic output
(not secure)
Brown +24VDC Voltage supply 24VDC
Green Lock Lock input
Yellow In 2 OSSD 2 input
1)
Gray Output signal switching device
(OSSD) 1
Output OSSD 1
Pink Output signal switching device
(OSSD) 2
Output OSSD 2
Blue 0V Voltage supply 0VDC
Red In1 OSSD 1 input
1)
1)
When used as an individual safety locking device or as the first safety locking device in a cascade: Apply
24VDC.
6 ELECTRICAL INSTALLATION
24
O P E R A T I N G I N S T R U C T I O N S | TR10 Lock 8019972/1CS1/2022-07-20 | SICK